The all new HBL Battery charger uses
16 Bit DSP Controller for switching
and control of Thyristor for
achieving desired DC output. The
charger output voltage, output
current and battery current,
including battery temperature
compensation are controlled by the
Digital Signal Processor. The
charger output parameters can be set
or adjust through keypad-display
provided on the front panel. It has
communication ports for local
monitoring using a PC and also
remote monitoring of measurements
and events as well as event history.
|
|
Features
Performance :
 |
Fully DSP Based SCR
controlled charger |
 |
Output voltage Range : 24V
to 500V DC |
 |
Output current Range : 20 to
2500A |
 |
Regulation: less than 1%
|
 |
Efficiency: more than 80% |
 |
Dynamic response: less than
150mS |
 |
Ripple at the output: less
than 1% |
 |
Less wiring, Easy of
testing, production and
installation |
Display and Data Monitoring:
 |
Measurements display over
128X64 Graphics LCD |
 |
11 special function keys for
user interface
|
 |
Customization of display
measurements and alarm
conditions upto 28 Alarms |
 |
User access for parameters
setting like output voltage,
output current limit,
battery current limit etc.,
from front panel display and
keypad, with password
protection |
 |
Momentary Load Test facility
with data logging for
battery health check |
 |
Provision for storing 500
events /faults |
Communication:
 |
MODBUS over RS485 |
 |
Live data (Measurements and
alarms) monitoring on Local
PC through USB |
 |
Remote data monitoring
through TCP/IP over Ethernet |
 |
Charger management Software
for monitoring data locally
as well remotely |
|

Downloads :
Product Leaflet
Dimension &
Electrical Data |